Carbon Monoxide Alarms: What Wisconsin Requires and Where They Go

Wisconsin's carbon monoxide rules are more specific than most owners realize, and the placement requirements depend on where the fuel-burning appliance is.

Which buildings are covered

The Wisconsin Department of Safety and Professional Services states that multi-unit residential buildings of three or more units with fuel-burning appliances must have carbon monoxide detectors. DSPS lists covered occupancies including hotels and motels, condominiums, apartments, dormitories, fraternities and sororities, convents and seminaries, jails and prisons, homeless shelters, community-based residential facilities, tourist rooming houses and bed and breakfast establishments. Hospitals and nursing homes are excluded.

One- and two-family dwellings fall under separate rules that the DSPS page above does not cover. If you own a single-family home or a duplex, confirm the current requirement with your municipal building inspector rather than assuming the multi-unit rules apply to you.

Where detectors go

Placement depends on where the appliance is, per the administrative rule DSPS cites (SPS 362.0915):

  • Appliance inside the unit, such as a gas range: a detector is required in that unit, near the sleeping room.
  • Appliance outside the unit, such as a shared gas fireplace: no detector is required inside the unit if one is installed on the ceiling between the appliance and the unit.
  • Forced-air furnace: a detector is required in the first room or area served by each main duct leaving the furnace, plus either alarm signals transmitted to all served units and a staffed monitoring location with fire department notification, or a detector in every fourth unit on the same floor.
  • No combustion appliances in the unit at all: no detector required.

The underlying statute, Wis. Stat. s. 101.149, puts detectors in a unit "outside of each separate sleeping area in the immediate vicinity of the sleeping rooms," and requires one inside a sleeping room that contains a fuel-burning appliance or has an attached bathroom containing one.

The owner's duties

Owners must install detectors according to the manufacturer's instructions and use only devices bearing a UL listing mark or a comparable independent certification mark. Detectors must be reasonably maintained per the manufacturer's instructions.

The deadline worth memorizing: when an occupant gives written notice that a detector is non-functional, or was removed by someone other than the occupant, the owner must repair or replace it within five days of receiving that notice. The same five-day window applies after written notice from a certified inspector.

Tampering carries real penalties. Under the statute, removing, disconnecting or taking the batteries out of an installed detector, outside of inspection, maintenance or replacement, is punishable by a fine of up to $10,000, up to nine months' imprisonment, or both for a first offense, with a second offense classified as a Class I felony. Uncorrected violations found on inspection carry a $50 per day forfeiture.

This is a plain-language summary of published state guidance, not legal advice. Rules change and municipalities can be stricter. Confirm specifics with your local building inspector.